Description
Technical Specifications: Model 2 (2U High-Density PDU)
Configuration: 2U Rackmount, Front & Rear Access Input Rating: 240V, 30A Plug Type: NEMA L6-30P Power Cord: 15ft (4.5 meters)
1. Panel Layout
- Front Panel:
- 1 x Digital Ammeter (Master Display)
- 2 x 20A Circuit Breakers
- 4 x IEC C19 Outlets (All with Auto-Locking feature)
- Rear Panel:
- Cable Entry Point
- 20 x IEC C13 Outlets
2. Circuit & Load Distribution (Dual Bank System)
The PDU is divided into two independent branches for load balancing:
- Bank 1:
- Control: Protected by Breaker 1 (20A)
- Outlets: 2 x Front C19 + 10 x Rear C13
- Bank 2:
- Control: Protected by Breaker 2 (20A)
- Outlets: 2 x Front C19 + 10 x Rear C13
3. Internal Wiring Specifications
- C19 Connections: AWG #12 wire (to support high-current equipment)
- C13 Connections: AWG #14 wire
- Safety: 4 x C19 outlets must include Auto-Locking mechanisms